태양열 구동 흡수식 냉동기의 작동성능 특성 연구

백남춘, 이진국, 윤응상 et al. · 한국태양에너지학회 학술대회논문집 · 1999

Design, manufacturing and performance analysis of solar driven single effect absorption chiller were made for the target of cooling capacity 5 RT, COP 0.7 with no refrigerant circulation pump. As results, refrigerator was operated above hot water temperature of 80℃ and it showed cooling capacity of 3.5 RT and COP of 0.5~0.6. The effects of the hot and chilled water temperature, cooling water temperature, solution circulation ratio and mass flow rate on the cooling capacity and COP were investigated to study the operation performance using simulation program.

Cited by 0 works.