To improve of the cooling performance of a CO₂ cycle, a CO₂ air-conditioner using two-stage compression cycle was tested with a variation of compressor frequency ratio. The cycle options include a basic cycle, a cycle with an intercooler, a cycle with an IHX(internal heat exchanger), and a cycle with an intercooler and IHX. The results show that the cycles with the intercooler, IHX, and intercooler and IHX improved the cooling performance significantly at all frequency ratios. The cycle with the intercooler, the cycle with the IHX and the cycle with the intercooler and IHX improved the cooling COP by 7, 12, and 15% over the basic CO₂ cycle.