그루브가 형성된 판형 열교환기식 액체 제습기에서의 열 및 물질전달
전동순, 문지현, 김선창 et al. · 대한설비공학회 하계학술발표회 논문집 · 2011
In this study, experimental investigations have been carried out to examine heat and mass transfer of a grooved plate heat exchanger type liquid dehumidifier. LiCl aqueous solution is employed as a working fluid. Mass flow-rate of LiCl aqueous solution and relative humidity of precess air were selected as experimental conditions. As results of heat transfer coefficient and mass transfer coefficient of LiCl aqueous solution were 0.11∼0.12 ㎾/㎡℃ and 11.2×10 ̄?~17.8×10 ̄? ㎧ respectively.
Cited by 0 works.