HFC 혼합냉매의 풀비등 열전달계수 측정 및 평가

고영환, 박진석, 정동수 et al. · 대한설비공학회 학술발표대회논문집 · 1998

Pool boiling heat transfer from horizontal smooth tubes has been experimentally investigated for pure fluids of R12, R22, R134a, R125, R32 and mixtures of R32/R125, R32/R134a, R125/R134a. The experimental apparatus is specially designed for plain tubes, similar to the real system with the use of the secondary fluid of water as a heat source rather than conventional electric heat source. Data were taken in the order of decreasing heat flux, starting at 100㎾ /㎡K and ending at 5㎾/㎡K. Special care was taken on elucidating the dependence of heat transfer reduction on mixture composition, heat flux and phase equilibrium diagram. This reduction is a function of the mixture composition and more prounced with an increase in heat flux. Experimental data are compared with available correlations developed for pure refrigerants by Stephan & Abdelsaram, Gorenflo and Cooper, and for binary mixtures by Stephan & Korner, Thome and Thome & Shakir. Thome & Shakir's correlation is found to predict heat transfer coefficients for the present mixtures well within the 15% accuracy.

Cited by 0 works.