실내 공기정화 시스템에 의한 실내 오염입자의 제거특성에 관한 실험적 연구

김성찬, 이창건, 안영철 et al. · 설비공학논문집 · 2003

The purpose of this study is to analyze the particle removal characteristics of a commercial air cleaner based on the electrostatic precipitator. The air cleaner consists of a positive corona precharger to precharge particles and a collector to remove the charged particles. The test for particle removal efficiency is conducted with tobacco smoke particles of 1.27㎛ in mass median diameter. The result of one-pass filtration test shows that the filtration efficiency is more than 90% for the particles larger than 2.5㎛, while the efficiency for the particles of 0.5~1.0㎛ in case of 4.18CMM is 70%. For the test room of 5,800×3,400×2,600㎣, the concentration of tobacco smoke particles decreases up to 30% of initial values within 30 minutes due to natural reduction and up to 90% of initial values within 30 minutes with the air cleaner operation.