경년변화에 따른 상업건축물의 소방시설 변화와 불량특성에 관한 연구

나욱정, 이호영, 홍원화 · 대한건축학회 논문집 - 계획계 · 2011

It is essential to check the function of fire protection system to minimize the fire damage. However, it is hard to ensure that the fire protection system works properly because it is rarely used and it takes long time to be discarded and renewed. Therefore, this paper investigates the kinds of fire protection system in details targeting the buildings in central commercial district which has a variety of potential fire hazards. The annual variations and malfunctioning characteristics are compared and analyzed by conducting visual inspection and function checks about fire protection system. As a result, it is found that the buildings in existence for more than 20 years have 18.7% more defective fire extinguish, 23.5% more defective indoor hydrant, 15.9% more defective automatic fire alarm system, and 6.4% more defective emergency exit sign comparing to the buildings in existence for less than 10 years.

Cited by 0 works.