전차선로에 유기되는 전압에 대한 원인분석 및 대책방안 연구

김환섭, 이기승, 임형길 · 한국철도학회 학술발표대회논문집 · 2012

When the voltage induced in pressureless the Catenary electric car tracks worker to check the shock and trauma caused by the crash are exposed to such risk, the Catenary Equipment by circulating currents, etc. there is the probability of accidents. Seoul Metro Line 4 in the operating and sales after the end between Main Line and the train depot on Main Line Catenary electric car tracks even if the corresponding circuit breaker to open 0 ~ 400 [V] so that the voltage was being induced. The cause of KEPCO 154kV high voltage transmission lines connected to substation Now on voltage induced in the same main line and vehicle-based sections separated by an insulating span view of the device due to poor performance, but the voltage induced in electric car tracks To investigate the exact cause of the real catenary to measure the voltage induced in a digital recorder in order to determine the path and the voltage conversion device which utilizes its own research has been carried out. In this paper, the voltage induced in electric car tracks and analyzed to determine the cause of the process and are reviewed to present its solution.

Cited by 0 works.