업무용 건물에 적용된 지열 히트펌프 시스템의 성능 예측

손병후, 권한솔 · 대한설비공학회 동계학술발표회 논문집 · 2013

Geothermal heat pump(GHP) systems have become an efficient alternative to conventional cooling and heating methods due to their higher energy using efficiency. These systems use the ground as a heat source in heating and a heat sink in cooling mode operation. The purpose of this simulation study is to evaluate the performance of a hypothetical GHP system in an office building and to assess the energy saving effect against existing HVAC systems(boiler and turbo chiller). We collected monthly energy consumption data from an actual office building(32,488.1 m²) in Seoul and then modeled to calculate the hourly building loads with EnergyPlus. In addition, we used GLD(Ground Loop Design) v.7.1.37, a GHP system design and simulation software tool, to evaluate hourly and monthly performance of the GHP system. The energy consumption for the GHP system based on the hourly simulation results were estimated to be 582.6 MWh/year for cooling and 593.2 MWh/year for heating, while those for the existing HVAC systems were found to be 674.5MWh/year and 2,496.4 MWh/year, respectively. The seasonal performance factor(SPF) of the GHP system was also calculated to be in the range of 3.37∼4.28.

Cited by 0 works.