외기전담 시스템 기반 초고층 공동주택 중앙 환기시스템의 에너지 절감효과 분석
김민휘, 김진효, 권오현 et al. · 한국태양에너지학회 학술대회논문집 · 2009
This paper investigates the energy saving potentials of a dedicated outdoor air system (DOAS) applied to a highrise apartment building. As for a typical 132-㎡ apartment unit, two different HVAC systems; centralized DOAS-Ceiling Radiant Cooling Panel and decentralized Energy Recovery Ventilator-Packaged Air Conditioner were installed. Transient behavior and control characteristics of each system were modeled numerically using a commercial equation solver program, and annual cooling coil load and heating load reduction potentials were compared. The research shows that DOAS-Ceiling Radiant Cooling Panel system can reduce the cooling coil load over 21% annually compared with the current Energy Recovery Ventilator-Packaged Air Conditioner pair. In addition, over 40% of annual ventilation heating load can be reduced by use of DOAS.
Cited by 0 works.