인버터 열펌프의 모세관 변화에 따른 시스템 성능특성의 실험적 연구
최종민, 김용찬, 김종엽 et al. · 대한설비공학회 학술발표대회논문집 · 1996
An experimental study was performed to investigate the optimum cycle of a inverter heat pump as a function of frequency. The performance of the inverter heat pump with the rated cooling capacity of 3550 ㎈/h was measured with a variation of frequency, indoor and outdoor temperature, and length of capillary tube in the psychrometric test room. As a base case, the inverter heat pump with the standard capillary tube length of 1000㎜ which was optimum size for the frequency of 60㎐ and ASHRAE Test condition. A was tested by varying frequency from 30㎐ to 80㎐. Then, the optimum cycles were investigated by varying the length of capillary tube at each frequency levels of 30, 60 and 80㎐. Based on the experimental data, the change of system characteristics between the optimum and the base case were analyzed for each selected frequency levels. Generally, for low frequency level(30㎐), the larger length of the capillary tube compared with the standard size showed the higher EER, while for high frequency level(80㎐) the smaller length of the capillary tube showed the higher EER.
Cited by 0 works.