혼합배전계통에서 지중선로의 다중접지 변경여부에 따른 과전압 해석 및 평가
정석산, 이종범 · 대한전기학회 학술대회 논문집 · 2010
In 22.9 [㎸] distribution systems, underground cables are provided with multiple-point grounding in which each neutral line of the distribution cable lines (A, B, C phases) is 3-wire common grounded at every connecting section. Therefore a case where the multiple-point grounding method change end-point grounding to relieve construction cost and potential risk such as water leakage at the connection point. This paper describes the difference of both grounding system ; one is the present grounding system, the other one is end-point grounding system. Simulation results show possibility that new grounding method could apply to real distribution system.