루버핀형 증발기의 공기측 성능에 대한 유동깊이의 영향
김만회, 박환영 · 대한설비공학회 학술발표대회논문집 · 1999
The effect of flow depth on the air-side thermal performance for brazed aluminum evaporators has been evaluated experimentally. A series of tests were conducted for thirty samples of louvered fin heat exchangers with different geometrical parameters such as flow depths, louver angles and fin pitches. The test was performed using a heat exchanger test facility for air-side Reynolds number based on louver pitch in the range of 80-400 and tube-side water flow rate of 320 ㎏/h. The dry- and wet-bulb temperatures of the frontal inlet air for heat exchangers were 27℃ and 19℃, respectively and the inlet water temperature was 6℃. The air-side heat transfer and pressure drop data for cooling and dehumidifying conditions were presented, compared with those for the dry surface coils.
Cited by 0 works.