멀티패스 밀폐식 냉각탑의 관경변화 특성
심규진, 이호생, 김은필 et al. · 대한설비공학회 동계학술발표회 논문집 · 2008
This paper presents experimental result of characteristics about Closed circuit Cooling Tower having a rated 2RT. The experimental apparatus has been set-up with a conventional type system. The test section is heat exchangers of cooling tower that consist of different vertical tubes, 15.88㎜ with 10 rows and columns and 19.05 ㎜ with 8 rows and 12 columns. The main results were summarized as follows : The values of heat and mass transfer coefficients of cooling tower operating with two paths are higher than these with one path. Cooling capacity per unit volume using 15.88㎜ tubes are higher than 19.05㎜ tubes.