반도체 클린룸용 증기가습 및 수분무가습 외기공조시스템의 연간 에너지소비량 비교분석 수치해석
김기철, 유경훈, 신대건 et al. · 대한설비공학회 동계학술발표회 논문집 · 2011
In a recent large-scale semiconductor manufacturing clean room, the energy consumption of an outdoor air conditioning system to heat, humidify, cool and dehumidify incoming outdoor air represents about 45 % of the total air conditioning load required to maintain a clean room environment. In particular the energy consumption to humidify the outdoor air in wintertime is enormous. Therefore, the evaluation and comparison of the annual energy consumption of steam humidification and water spray humidification outdoor air conditioning systems has a significant meaning for reducing the outdoor air conditioning load of the clean room. In the present study, a numerical analysis was conducted to obtain the annual electric power consumption of the two outdoor air conditioning systems. It was shown from the numerical results that the water spray humidification outdoor air conditioning system exhibited lower electrical power consumption and was more energy-efficient for the wintertime operation than the steam humidification one.
Cited by 0 works.