메쉬접지극의 매설깊이 변화에 따른 특성 분석
김종수, 최홍규, 박준열 et al. · 한국조명·전기설비학회 학술대회논문집 · 2010
Grounding electrodes with higher burial depths are evaluated to have better performance, due to the domestic practice that puts the grounding resistance as the standard of performance evaluation, while grounding resistance decreases as the burial depth increases. However, the performance evaluation of mesh grounding electrodes for uses in power stations and substations should include not only grounding resistance but also the dangerous voltage(mesh voltage and step voltage) in precaution towards the increase of land-voltage at the occurrence of ground-fault. This article investigates on the changes in grounding resistances and dangerous voltage(mesh voltage and step voltage) according to the changes in burial depths of mesh grounding electrode.