고분벽화의 보존을 위한 고분내부 온열환경요소의 설정범위와 처리부하
진재훈, 엄태윤 · 대한설비공학회 학술발표대회논문집 · 2014
This paper aims to clarify that the setting range of thermal environmental elements and the cooling load for the conservation of mural paintings in ancient tomb, Songsanri No. 6, Korea. As the results, (1) it was shown that the air temperature in the tomb must be to maintain 17 ℃ below through the year. (2) We confirmed that the mean of cooling load for the conservation of the mural paintings in Songsanri No. 6 was about 900W by the cooling load calculation using the measuring data in tomb from 2012 to 2013. This value was very small as 1/14 compared with the capacity of the cooling system installed in the tomb from 2010.