지역냉방용 저온재생 고분자 제습로터 개발
한민영, 문현기, 김건우 · 대한설비공학회 하계학술발표회 논문집 · 2012
This paper describes the development of a low temperature regenerative desiccant rotor for the district cooling using the SDP(Super Desiccant Polymer). The moisture sorption capacity of the super desiccant polymer is 4 to 5 times larger than those of common desiccant materials such as silica gel or zeolite. The super desiccant polymer is usually produced as granules, and so it is laminated by placing it between two thin papers and pressing them to join into the sheet material. Then the sheet material is corrugated, cut and winded itself round the tube to produce the desiccant rotor with the size of 600×120(diameter×length, mm). The desiccant rotor cassette consists of 1 desiccant rotor contained electrolytic galvanized iron sheet with welded rims, geared motor and timing belt. The dehumidification performance was tested in a climate chamber. The relevant tests were carried out at the process air inlet temperature of 32℃, the regeneration air inlet temperature of 60℃ and the inlet dew-point temperature of both the process air and the regeneration air of 18.5℃. The performance is compared with one of very common commercial desiccant rotor. It is shown that the performance is superior to that of the commercial product. Currently the durability test is going on.