복사-대류 겸용 하이브리드 냉방기
변호원, 오왕규, 김내현 et al. · 대한설비공학회 동계학술발표회 논문집 · 2008
The hybrid air-conditioner, where air is cooled both by convection and radiation, is developed. The indoor unit of the air-conditioner consists of radiation panel and dehumidification coil, where refrigeration R-134a is supplied by independent refrigeration cycles. Optimum refrigerant charge was 750g for both cycles. Optimum evaporation pressure was 3.7 bar for the radiation panel cycle and 3.9 bar for the dehumidication cycle. The cooling capacity of the radiation panel was 1.01 ㎾ and that of the dehumidification coil was 0.94kW, which yielded COP of 3.3.