배전용 폴리머 피뢰기의 전기적 특성시험
권태호, 이병성, 송일근 et al. · 2004
This paper describes the electrical characteristics of the polymer lightning arresters(L.As) used to protect distribution lines and power facilities from surge. For the relative comparison, the characteristics assessment was done for 2 states of L.As before and after water immersion treatment. The L.As for the comparative test were immerged with water of 95[℃] considered a severe condition. After the immersion treatment, the assessment was carried out for material analyses in chemical structure(FTIR : fourier transform infrared spectrophotometer). Electrical performance measured insulation resistance measurement, leakage current measurement, critical operation voltage measurement etc.. In addition to, the results were compared with those for the L.As deteriorated in the field. Thus, the accelerative deterioration degree of polymer materials by immersion treatment was evaluated, by which the structural defects of the polymer L.As could be inferred.