축열조 디퓨져 형상이 성층화에 미치는 영향

이상남, 이영수, 박성룡 et al. · 대한설비공학회 동계학술발표회 논문집 · 2001

The stratification effect was investigated with three different types of diffuser shape in a thermal storage tank with variation of diffuser diameter, velocity, Froude number etc. Its effect was estimated by the degree of stratification. No matter of diffuser diameter and shape, the degree of stratification was the best as the Froude number gets closer to 1. In the case of a curved diffuser, when its diameter is a quarter of tank diameter and ejection velocity in a diffuser is approximately 0.2 ㎧, the Froude number was almost 1. In the case of a flatted diffuser, when ejection velocity was 0.05 ㎧, the Froude number was 1.5. Both cases which Froude number were nearer 1, shown the good degree of stratification.