대지저항률 측정의 정확도 평가

이복희, 이승훈, 최종혁 et al. · 한국조명전기설비학회 추계 학술발표회논문집 · 2010

Ground resistance is determined by the shape of grounding electrode and soil resistivity near the buried ground rod. The soil resistivity is practically measured by Wenner four-point method or three-point method measuring the ground resistance of the driven test rod. In this paper, the measurement accuracy of soil resistivity and the relation between the test electrode spacing in four-point method and the length of the driven test rod in three-point method are evaluated. The results obtained from both measuring methods are dependent with the soil structure and measuring conditions. The soil resistivity measured with a specified length of the driven rod in three-point method was in agreement with the result measured with a specified electrode spacing in Wenner four-point method.

Cited by 0 works.

Authors