제습증발냉각기반 전외기 공조시스템의 겨울철 운전에너지 성능 실증 분석

김민휘, 조수영, 정재원 · 대한건축학회 학술발표대회 논문집 · 2014

This study is to investigate the energy saving potential of desiccant and evaporative cooling-assisted 100% outdoor air system (LD-IDECOAS) in winter season. The pilot system was installed in office building and a conventional variable air volume (VAV) system was also installed to compare the energy performance of the proposed system. The temperature, humidity, and airflow sensors are installed on various measuring point to estimate the effectiveness of indirect evaporative cooler (IEC) and sensible heat exchanger(SHE). It was found that the effectiveness of IEC and SHE showed 85% and 69%, respectively. One can conclude that the LD-IDECOAS showed significant operating energy was saved via conventional VAV system.

Cited by 0 works.