실내 모멘텀 소스 변화에 따른 환기성능 비교
노광철, 오명도 · 대한기계학회 춘추학술대회 · 2005
The numerical study was performed for the comparison of ventilation performance with variations of indoor momentum source. CO₂ concentration and local mean air-age of the room were calculated with respect to the intensity and the location of momentum source, occupancy and methods of room air diffusion. The numerical results showed that ventilation performance of the room was strongly affected by methods of room air diffusion. Their maximum difference of CO₂ concentration between a mixing system and a displacement one was about 300ppm in the occupied zone of the same-sized room. And we found out that ventilation performance is getting better or worse with variations of the intensity and the location of momentum source. It is due to that the intensity and the location of momentum let the residence time of air be longer or shorter in the room.