흡수식 냉온수기 희용액 펌프 인버터 주파수 설계에 관한 연구

Younggy Shin, 조현욱, 남상철 et al. · 대한설비공학회 학술발표대회논문집 · 2010

In an absorption chiller, solution is circulated by a solution pump with an inverter to vary throughput depending on operating conditions. For optimal operation, the solution level in the high temperature generator should be kept constant. However, a sensor for measuring continuous level is not available because of high solution temperature. Instead, level switches are used and hence feedforward control is a common practice. In the study, inverter frequencies are estimated from a dynamic simulation model and pump performance curve. The values are compared with those implemented in real chillers. It was found that the frequencies used in real chillers are larger than those needed in circulation flow rates. It was intended to prevent system shut-off caused by dry-out. However, it is necessary to minimize the excessive frequency setting in order to reduce frequent pump stops and the range of solution level for continuous pump operation.