헬리컬 코일 관내의 2상유동 압력강하에 관한 연구
사용철, 유승문, 이준식 · 대한설비공학회 학술발표대회논문집 · 1999
Two-phase pressure drop of R-113 in uniformly heated helically coiled tubes was measured. The coiled tubes of 10.9㎜ I.D.were helically bent to have coil diameters of 0.20, 0.33 and 0.57m. These tubes were electrically heated by AC. Experiments were conducted to measure pressure dop values with mass flux ranging from 300 to 900 ㎏/㎡s, heat flux ranging from 15 to 60 ㎾/㎡ and inlet pressure ranging from 0.2 to 0.8 ㎫. The frictional pressure drops decreased as coil diameter ratio and system pressure increased. Two-phase frictional multipliers, defined by the ratio of two-phase frictional pressure drop to single phase frictional pressure drop, were linear to equilibrium quality and affected mainly by system pressure and coil diameter ratio. The correlation of two-phase frictional multiplier was proposed in terms of the liquid/vapor density ratio and the coil diameter ratio.