The main object of this study was to investigate the performance characteristics such as refrigerating capacity, compression work, and coefficient of performance of the R-22 two-stage compression refrigeration systems, The apparatus consisted of 0.5 HP and 1 HP hermetic reciprocating compressors for the high and low stage sides respectively, The experiments covered a range of refrigerant flow rate from 24 to 84 ㎏/h, and the inlet temperature of cooling water in the condenser, and heat source water in the evaporator from 20 to 30 ℃. The results showed that the refrigerant flow rate was more effected on the refrigerating capacities, the works of compression and the coefficient of performance of two-stage compression systems than inlet temperature of heat source water, And they were decreased with increasing inlet temperature of cooling water.