교류철도의 자동통과시스템에 대한 이상현상 문제점 연구

한문섭, 신효범, 창상훈 et al. · 대한전기학회 학술대회 논문집 · 2012

AC power supply system supplies power to railroad sections. In order to prevent collision of disordered power suppliers, neutral sections are constructed near the substations and sectioning posts. For these reasons, the study on automatic changeover system is in process. Also in order to verify the theory, field experiments on system constructed at Yongpo-ri SSP?which is included in Dae-bule pilot model railroad?is on the stage. In this paper, power transfer experiment results, which conducted by passing practical rolling stock(EL-8200s) through the neutral section where the power supplier is adopted, are presented. In order to measure the inrush current and abnormal phenomenon, the power transfer experiment had conducted with VCB switches and thyristor switches. Also in order to analyze the undergoing phenomenon affected by traction driving.

Cited by 0 works.