해수열-지열 복합이용시스템의 타당성 평가연구

이호생, 정영권, 정동호 et al. · 대한조선학회 학술대회자료집 · 2011

The paper presents the analysis for cycle performance of ocean thermal energy conversion(OTEC) and seawater air-conditioning(SWAC) with deep ocean water and geothermal heat. The basic thermodynamic model for cycle is Rankine cycle and the geothermal water and deep seawater were adapted for the heat source of evaporator and condenser, respectively. The cycle performance such as gross power, sea water and geothermal water flow rate etc. was analyzed on the flowrate variation of deep seawater . The compressor work in case of seawater heat pump system showed 21.7% lower and the COP showed 19.8% higher than that of the existing air-cooled heat pump system when the deep seawater from OTEC is used for the heat source of SWAC.

Cited by 0 works.

Authors