인버터 열펌프의 주파수 및 모세관 길이 변화에 따른 시스템 성능특성의 실험적 연구

최종민, 김용찬, 김종엽 et al. · 설비공학논문집 · 1997

An experiment study was performed to investigate the optimum cycle of an inverter heat pump as a function of frequency. The performance of the inverter heat pump with the rated cooling capacity of 4141W(3550㎉/h) was measured with a variation of frequency, indoor and outdoor temperature, and length of capillary tube in the psychrometric test room. As a base case, the inverter heat pump with the standard capillary length of 1000㎜ which was optimum size for the frequency of 60㎐ and ARHRAE Test condition A was tested by varying frequency from 30㎐ to 80㎐. Then, the optimum cycle was invesigated by varying the length of capillary tube at each frequency levels of 30, 60 and 80㎐. Based on the experimental data, the change of system characteristics between the optimum and the base case were analyzed for each selected frequency levels. Generally, for low frequency level(30㎐), the longer length of the capillary tube compared with the standard size showed the higher EER, while for high frequency level(80㎐) the shorter length of the capillary tube showed the higher EER.