알루미늄 열교환기의 경사각도가 공기측 성능에 미치는 영향
김만회, 박환영, 윤백 et al. · 대한설비공학회 학술발표대회논문집 · 2001
The present work studied the effect of an inclination angle on the air-side thermal hydraulic performance of a brazed aluminum heat exchanger which is composed of multi-louvered fins and flat tubes with micro-channels. For heat exchangers with a louver angle of 27˚, fin spacing of 1.4 ㎜ and flow depth of 20 ㎜, a series of test for dry and wet surface conditions were conducted for the air side Reynolds numbers of 100-300. The inclination angles from the vertical position were ±30˚, ±45˚ and ±60˚. Heat transfer performance for both dry and wet conditions was not influenced significantly by the inclination angle, while the pressure drop increased consistently with the increase of inclination angle.
Cited by 0 works.