양수발전소 동기전동기의 기동제어 알고리즘에 관한 연구
강승우, 박신현, 김장목 et al. · 전력전자학술대회논문집 · 2003
The large synchronous motor for the pumped-storage plant(or SFC : Static Frequency Converter) has to be brought up to 100% rated speed and synchronized with the AC power network. Starting the motor from rest is achieved by switching current into the stator winding so that interaction between tins stator current and the rotor flux will cause the correct direction of torque to be developed so that the motor turns m the required direction. Starting ranges of the synchronous motor are divided into three regions. The first region is at standstill, the second that is called by the forced commutation is from standstill to 5-8% of rated speed, and the third, which is called by the natural commutation, is from 5-8% of rated speed to 100% rated speed So This paper describes three regions of the control techniques of the pumped-storage synchronous motor drive