도시철도 역사 냉방 시스템 가동에 따른 대합실 및 승강장에서의 온도 분포 연구

장용준, 류지민, 정호성 et al. · 한국철도학회 학술발표대회논문집 · 2014

The various R&D projects regarding the high efficiency of energy in the subway station are going on. The percentage of electricity consumption for air conditioner in the subway station is more than 65%. In this study, the temperature distribution in the lobby and platform of subway station is investigated under the condition of operating of air conditioning. Shingumho station(The line # 5, Depth: 46m) has been selected as a simulation model. The ventilation mode is ordinary state and the cool air of 47,316m³/h is supplied and the returned air of 33,980m³/h is exhausted in the lobby and the cool air of 33,968m³/h is supplied and the returned air of 76,190m³/h is exhausted in the platform. The temperature of cool supplied air in the diffusers is 10℃. The numbers of ventilation diffuser are 94 and 222 in the lobby and in the platform, respectively. Total of 7.5 million grids were generated for this simulation. In order to enhance the efficiency of calculation, parallel processing by MPI was employed and Large Eddy Simulation method was adopted.

Cited by 0 works.