슬래브-기둥 접합부의 이력거동에 대한 기둥 형상비의 영향
조인중, 최명신, 안종문 et al. · 대한건축학회 학술발표대회 논문집 - 구조계 · 2007
In this investigation, results of laboratory tests on four reinforce concrete flat plate interior connections with elongated rectangular column support which has been used widely in tall residential buildings are presented. The purpose of this study is to evaluate an effect of column aspect ratio(β c =c₁/c₂=side length ratio of column section in the direction of lateral loading (c₁) to the direction of perpendicular to c₁) on the hysteretic behavior under earthquake type loading. The aspect ratio of column section was taken as 0.5~3(c₁/c₂=1/2, 1/1, 2/1, 3/1) and the column perimeter was held constant at 1200㎜ in order to achieve nominal vertical shear strength(V c ) uniformly. Other design parameters such as flexural reinforcement ratio of slab and concrete strength was kept constant as p=1.0% and f ok =40㎫, respectively. Gravity shear load(V g ) was applied by 30 percent of nominal vertical shear strength(0.3V o ) of the specimen. Experimental observations on punching failure pattern, peak lateral-load and story drift ratio at punching failure, and stiffness degradation and energy dissipation in the hysteresis loop were achieved and discussed in accordance with different column aspect ratio. Eccentric shear stress model of ACI 318-05 was evaluated with experimental results. A fraction of transferring moment by shear and flexure in the design code was analyzed based on the test results.