국가 고전압 표준용 직류고전압 분압기의 측정능력 향상
이상화, 장석명, 최장영 · 2014
The main measurement uncertainty factors in DC high-voltage dividers for a national high-voltage standard are the measurement uncertainty of low-voltage arm and the stability of a high-voltage supply. In this study, the uncertainties by the two factors are greatly improved. As a result the measurement uncertainty for the DC high-voltage divider is reduced from 16×10 -6 (k = 2) to 8×10 -6 (k = 2) which is at international level.
Cited by 1 works.