초임계압 열전달 특성에 관한 실험 연구

강경호, 윤영중, 박종국 et al. · 대한기계학회 춘추학술대회 · 2008

A series of experiments have been performed in a vertical tube of 9.4 ㎜ inner diameter using the Freon, HFC-134a as working fluid medium under the supercritical pressure range. Two kinds of experiments, i.e. steady-state and pressure transient, have been carried out. As for the steady-state heat transfer experiment, the mass flux was in the range between 600 and 2000 ㎏/㎡s and the maximum heat flux was 160 ㎾/㎡. The selected pressures were 4.1, 4.3 and 4.5 ㎫ which correspond to 1.01, 1.06 and 1.11 times the critical pressure, respectively. In the pressure transient experiments, the inlet pressures were varied from 3.8 to 4.5 ㎫ and vice versa in the pressure transient simulations. In this study, heat transfer correlation and criterion for the heat transfer deterioration are suggested under the supercritical pressures. And also heat transfer characteristics during the pressure transient are examined.