선형조인트 내화충전구조 시스템 내화물(암면)의 압축 및 보온재 여부에 따라 내화성능에 미치는 영향에 관한 실험적 연구

조경숙, 여인환, 전기수 et al. · 대한건축학회 학술발표대회 논문집 · 2013

It shall be mandatory by the building code that fire resistance system should be install for prevent to fire spread through linear joint between slab and curtain-wall in high-rise building in Korea. This study intend to fine out effect of fire resistance performance of fire resistance system depend on compression of mineral wool and with/without insulation. We tested 4 specimens in fire by guideline for test of fire resistance system. The results was failed to, the specimen which was mineral wool without compression and curtain wall with insulation, arise flame to insulation at 75 minutes after starting fire test, surface temperature of linear joint was over 180K.

Cited by 0 works.