화재 시 제트 팬 위치에 따른 제연해석
김지성, 안종환, 강신형 et al. · 대한설비공학회 동계학술발표회 논문집 · 2001
In this study, jet fans is installed with 4 cases in the long tunnel; inlet-side setup, middle-side setup, outlet-side setup, and dispersion setup. Fire car is bus, of which fire size is 20㎿. And fire car locates at 100m, 700m, 1500m position from tunnel inlet respectively. FLUENT, commercial finite-volume code, is used to analyze the performance. The velocity profile, CO₂ concentration, temperature distribution are examined for analysis. Performance of smoke control is compared by the backlayering length. Consequently, Inlet-side setup of jet fans is a little more efficient than other cases considering the fire occurrence frequency in tunnel.