에너지 슬래브 적용 지열원 열펌프 시스템의 냉방성능 특성
김남태, 최종민 · 대한설비공학회 학술발표대회논문집 · 2010
Energy foundations and other thermo-active ground structure, energy wells, energy slab, and pavement heating and cooling represent an innovative technology that contributes to environmental protection and provides substantial long-term cost savings and minimised maintenance. The paper focuses on earth-contact concrete elements that are already required for structural reasons, but which simultaneously work as heat exchangers. Pipes, energy slabs, filled with a heat carrier fluid are installed under conventional structural elements, forming the primary circuit of a geothermal energy system. The natural ground temperature is used as a heat source in winter and for cooling in summer. Hence no additional elements have to be installed below surface. The primary circuit is then connected via a heat pump to a secondary circuit within the building. The system represented very high cooling performance due to the stability of EWT from energy slab. Daily average heat pump unit COP and system COP were 4.5 and 4.0, respectively in the cooling mode.
Cited by 0 works.