배전계통의 고장이 배전용 피뢰기에 미치는 영향

이복희, 강성만, 최휘성 et al. · 2004

There are unsymmetrical faults such as single line-to-ground faults, line-to-line faults, or double line-to-ground faults in overhead distribution system. Lightning surge arresters are stressed by system frequency overvoltages due to unsymmetrical faults. In this study, the unsymmetrical faults in three-phase four-wire overhead distribution systems were experimentally simulated, and characteristics of total leakage current of distribution surge arresters caused by these faults were investigated. Also, the variation aspects of total leakage current of distribution surge arrester caused by voltage variation were examined. As a result, abnormal voltages caused by voltage variation the line-to-line fault the two line-to-ground fault have a little effect of total leakage current on ZnO surge arrester. But the leakage current of ZnO surge arrester under single line-to-ground faults in solidly grounded systems was more than 20 times as compared with that under symmetrical states.