전력제어 반도체용 열파이프 냉각장치의 열전달 성능 연구
강환국, 김철주, 김재진 et al. · 대한설비공학회 학술발표대회논문집 · 1997
These days heat pipe typed cooling units have been widely applied to power controllers for railway substations to remove heat from power semiconductors(diodes or thyristor). The cooling units consist of a copper heating block for mounting the thyristor, 2~3 heat pipes and large number of aluminum Ems. The present study was to get fundamental informations over structure, design parameters and heat transfer performances of such a cooling unit. Series of operational test for a unit with 3 heat pipes were performed and its heat flow circuit was analysed from experimentally obtained data on wall temperature distribution. Its total resistance was ranged 0.02~0.03℃/W for a power 40W<Q<400W. The time, collapsed to get start the heat pipe, was approximately 17sec, and the wall superheat to initiate nucleation on the heated surface was about 30℃.