반도체 클린룸용 배기 열회수식 에어와셔 시스템의 에너지 소비량 실험
김형태, 송근수, 유경훈 et al. · 대한기계학회 춘추학술대회 · 2009
In the present study, an experiment was conducted to investigate saturation efficiencies of air washer, the energy consumption and heat recovery efficiencies for fin-coil type air washer systems. In recent semiconductor manufacturing clean rooms, the energy consumption of outdoor air conditioning systems represents about 45 % of the total air conditioning load required to maintain a clean room environment. Meanwhile, there is a large amount of exhaust air from a clean room. From an energy conservation point of view, heat recovery is therefore useful for reducing the outdoor air conditioning load for a clean room. In the present work, an energy-efficient outdoor air conditioning system was proposed to reduce the outdoor air conditioning load by utilizing an air washer to recover heat from the exhaust air. The proposed outdoor air conditioning system consisted mainly of a preheating coil, an air washer, two stage cooling coils, a reheating coil, a humidifier and two heat recovery cooling coils inserted into the air washer and connected to a wet scrubber.
Cited by 0 works.