저심도 대구경 지중열교환기의 설치 및 성능 연구

유규상, 박일문, 신현준 et al. · 대한설비공학회 학술발표대회논문집 · 2010

A ground-loop heat exchanger for the ground source heat pump system is the core equipment determining the thermal performance and initial cost of the system. The size and performance of the heat exchanger is highly dependent on the ground thermal properties - the ground effective thermal conductivity, the borehole thermal resistance and the undisturbed ground temperature. We were carried out some tests to investigate the effects of some parameters such as borehole length and grouting materials of the Large borehole ground-loop heat exchanger. The thermal response tests were conducted using a testing device for 4-different ground-loop heat exchangers. Ground effective thermal conductivity shows that cement grouting is 10% higher than soil grouting.