응축기용 튜브의 내부 나선 홈에 의한 열전달 특성과 압력손실에 관한 연구

한규일, 조동현 · 대한설비공학회 학술발표대회논문집 · 1995

Heat transfer performance improvement by fin and grooves is studied for condensation of R-11 on integral-fin tubes. Eight tubes with trapezodially shaped integral-fins having fin density from 748 to 1654fpm and 10, 30 grooves are tested. A plain tube having the same diameter as the finned tubes is also used for comparison. R-11 condensates at saturation state of 32℃ on the outside tube surface cooled by inside water flow. All of test data are taken at steady state. The heat transfer loop is used for testing single long tubes and cooling is pumped from a storage tank through rulers and flowmeters to the horizontal test section where it is heated by steam condensing on the outside of the tubes. The pressure drop across the test section is measured by means pressure gauge and manometer. The results obtained in this study is as follows : 1. Based on inside dimeter and nominal inside area, overall heat transfer coefficients of finned tube are enhansed up to 1.6 ~ 3.7 times that of a plain tube at a constant Reynolds number. 2. Friction factors are up to 1.6 ~ 2.1 times those of plain tubes. 3. The constant pumping power ratio for the low integral-fin tubes increase directly with the effective area to the nominal area ratio, and with the effective area diameter ratio. 4. A tube having a fin density of 1299fpm(fin per meter) and 30 grooves has the best heat transfer performance.