소형 흡수식 냉온수기의 추기장치 개발에 관한 연구
김용원, 백영호, 윤정인 · 대한설비공학회 학술발표대회논문집 · 1999
An absorption chiller/heater using LiBr and water as working fluid is usually designed to get chilled water of 7℃ in summer. In order to achieve this temperature the pressure in the evaporator should be retained at 0.8~0.9k㎩(6~7㎜Hg). But, by some reasons, if non-condensible gas inside of the machine increase during the operation, the inner pressure gets higher and the system will go to an unstable state. Therefore, purging the non-condensible gas out of the machine is very important for keeping the operating condition stable and good performance. In this paper a developed automatic gas purge system is described and experiments were carried out not only with the system itself but also by attaching the system to the absorption chiller/heater. The automatic gas purge system shows satisfying results in keeping the vacuum condition of the absorption chiller/heater.