역삼투압방식의 냉/온정수기 퇴수를 이용한 수랭식 응축기와 기존의 공랭식 응축기 성능비교

이재원, 정청우, 김성수 et al. · 대한설비공학회 하계학술발표회 논문집 · 2010

The reverse osmosis type water purifier is able to purify only about 20~40% of the tap water or underground water, and the rest is discarded. Generally, the cooling system of a small domestic cold & hot water purifier uses an air cooled type condenser. One disadvantage of this system is that the cooling capacity depends on the ambient conditions, therefore it needs a big size of heat exchangers. However, it is possible to solve this problem by reusing the drain water in the water cooled type condenser. The power consumption rate of the cooling system with the air cooled type condenser is estimated as 66.2W, while that with the a water cooled type condenser is estimated as 54.2W. Therefore, the water cooled type condenser reusing drain water is recommended to reduce the power consumption in the compressor.