This paper contains a simulation program to predict the capacity of a condenser coil used in an air-conditioning application. This simulation program is capable of accepting the two dimensional inlet air velocity profile and various refrigerant path configurations. The simulation program reveals the comparable capacity results in comparison of test experiment performances. Insulated wind tunnel facility, refrigerant supply unit and constant water bath have been used in the test experiments. Two types of condenser refrigerant flow path are tested and analyzed. The HCFC-22 is the working refrigerant in the test experiments. The relative error between air-side heat transfer and refrigerant heat transfer is 5.0%. The performance error between test and simulation bounds within 3.2% for Z type path and 8.7% for U type path.