임펄스전류에 의한 수직 접지전극 주변에서 전위간섭 영향 분석
조용승, 이복희 · 한국조명·전기설비학회 학술대회논문집 · 2011
When the ground current is injected into the adjacent ground electrode, the potential interference is caused between grounding electrodes. Ground potential interferences have been largely studied with power frequency fault currents. Many attempts to find a frequency-dependent grounding impedance report that the grounding impedance at high frequency is very different with the ground resistance. In this paper, the potential interference effects in the vicinity of vertical ground rod of 4 m long are measured according to the front time of the injected impulse current. The ground potential rises around the test ground rod of 4 m were measured and discussed. As a result, the ground potential rises and potential interference factor are decreased with decreasing the conventional grounding impedance. It was found that the lowering of conventional grounding impedance is critical to reduce the ground potential interference effects.
Cited by 0 works.