열펌프 난방 저온 운전조건에 대한 관내측 증발 열전달 특성
문동수, 서국정, 김용찬 et al. · 대한설비공학회 학술발표대회논문집 · 1998
Outdoor unit of the heat pump system is generally operating at low evaporating temperature in the heating mode. The enhancement of performance of outdoor unit is required to provide a proper heating capacity. In the present study, evaporation heat transfer coefficients were measured for smooth and micro-fin tubes with R-22 at low temperature that was corresponding to the operational conditions of heat pumps. Heat transfer measurements were performed on 3.0 m long smooth and micro-fin tubes with inside diameter of 6.18 ㎜ and 6.30 ㎜, respectively. The range of parameters covered includes evaporating temperature from -15 C to 5 ℃, refrigerant mass flux 117 ㎏/㎡s to 211 ㎏/㎡s, heat flux from 5 ㎾/㎡ to 15 ㎾/㎡. It was observed that evaporation heat transfer coefficients were increased as evaporating temperature was decreased. When test results of a micro-fin tube were compared with those of smooth tube at the similar test conditions, evaporation heat transfer coefficients of a micro-fin tube were from 40% to 60% higher.
Cited by 0 works.