예냉기를 이용한 대향류형 냉각탑에 관한 실험적 연구
김병태, 서무교, 박재홍 et al. · 대한설비공학회 동계학술발표회 논문집 · 2001
Pre-cooler is applied to decrease the inlet air-temperature, which is the main parameter of cooling tower performance. The thermal performance of pre-cooler is mainly affected by the velocity, temperature, water flow rate and humidity of the entering air. The experiments was performed for various stack numbers, water flow rate of 1.0~2.5 l/min, air velocity of 1.0~2.0 ㎧ and wet-bulb temperature 25~27℃ under the condition of dry-bulb temperature of 32℃. The characteristic value, KaV/L, was enhanced for the case of increased air velocity and decreased air-water ratio, L/G. According to the increment of stack numbers, wet-bulb temperature was decrease but pressure drop was increased. In this study, the effects of pre-cooler are experimentally investigated for counter cooling tower.