난방순환계통 변유량 제어에 따른 에너지 절감효과 예측

김용기, 이태원, 김다희 et al. · 대한기계학회 춘추학술대회 · 2011

Major energy savings can be made by simply enabling pumps to run at variable speeds over 30% in some cases. The heart of the energy saving principle of variable speed pumps is the basic hydrodynamic law that the power consumed by centrifugal pumps varies as the cube of impeller speed. But, heating water circulation pumps installed before year 2000 in the district heating system in Korea were adopted the CVF(Constant Volume Flowrate) control method over 10,000 units according to the data of KDHC. The main goal of this study was to estimate the effect for the VVF(Variable Volume Flowrate) control method of heating water circulation pumps by using the real measuring data(flowrate, differential pressure, etc.) and the performance characteristic curve of a variable speed pump. As the results, it was assumed that the total pumping electric power was saved up to over 43.5% by VVF control method in a apartment complex in Korea.

Cited by 0 works.